XTMF-100 intelligent digital display regulator product techn
Product technical data
Input form
thermocouple
B 400 ~ 800℃
S 0 to 1600 ° C
K 0 ~ 1300℃
E 0 ~ 800 ° C
T 0 ~ 400 ° C
Thermal resistance
Pt100-200 ~ 500℃
Cu50-50 ~ 150℃
linearity
0 to 10mA DC
4 to 20mA DC
0 to 5V DC
0 to 5V DC
Output form
control
Two-position: insensitive area range O. 1% ~ 10.0%, relay contact output.
Time ratio: Cycle 1 ~ 200 seconds ratio with 0.1% ~ 400.0% relay contact output.
Two-position PID: Cycle 1 ~ 200 seconds ratio with 0.1% ~ 400.0% integral time: O ~ 3600 seconds
Differential time: 0 ~ 3600 s relay contact output.
Continuous PID: proportional band 0.1% ~ 400.0% Integral time: O ~ 3600 seconds
Differential time: 0 ~ 3600 seconds 0 ~ 100mA (4 ~ 20mA) DC output.
Three-position PID: adjustable from 0.0 to 10% in insensitive zone
Relay contact output
Relay operation range 0.1 ~ 10%
Relay operation cycle 1 ~ 200 seconds
Valve position feedback signal: 0 ~ 100mA (4 ~ 20mA) DC
0 ~ 1KΩ resistance signal
Logical output: 24V DC 20 mA
Solid state relay output: Capacity 2A 250V AC
alarm
Two groups of relay contact output can be used for upper and lower limit alarm.
A process alarm can be used as an insurance device for the system, that is, once the measured value is greater than the process alarm set value, the output value of the instrument is cut to the output lower limit.
Process quantity output
0 to 100mA DC, 4 to 20mA DC, 0 to 5DC, 1 to 5VDC.
Power supply
Switching power supply: 86 ~ 264V AC 50Hz±5%
Power consumption: 6VA
Supply transmitter power: 24V DC, 50 mA