0550-7516155|Disclaimers|Sitemap中文RussianEnglish

Display instrument

Intelligent digital display regulator

Product description: XTMF/A/D/C-100 series is made of special chip, complete output and regulation
  • Tel:0550-7516155
  • Fax:0550-7513155
  • Email:ghdq@ghdqkj.com
Description

Product description: XTMF/A/D/C-100 series is made of special chip, complete output and regulation rules for choice, with power failure protection function, accuracy level 0.3%FS, with full input function, so that the instrument can play a table multi-purpose, linear input range can be transferred at will, display clear, intuitive, reliable and practical instrument installation structure.


Major technology


SMT surface mount technology is adopted


Switching power supply makes the instrument more lightweight.


With full input function, not only make the instrument with a table multi - purpose, increase the plasticity of the instrument.


With power failure protection function.


The accuracy was 5%FS± 1ding.


Two sets of breaker output flexible use, can be used for alarm, can also be used for regulation.


Linear input time range can be migrated at will.


It has very high performance-price ratio.


The display method is clear and intuitive.


Reliable and practical instrument mounting structure.


Resolution is 14bit.


With sensor error correction function.


Input form


Thermocouple B:0 ~ 1800℃ S:0 ~ 1600℃ K:0 ~ 1300℃ E:0 ~ 800℃


T:0 ~ 300℃ J:0 ~ 800℃ Wu-Re3-25 0 ~ 2000℃


Thermal resistance :Pt100: -100 ~ 200℃ -200 ~ 600℃


Cu50:0 ~ 150℃


Linear input


mV Input: 0 ~ 100mV.DC; 0 ~ 50mV.DC; 0 ~ 100mV.DC;


Voltage input :0 ~ 5V.DC; 1 ~ 5V.DC;


Current input: 0 ~ 100mA.DC; 4 ~ 20 ma.dc;


Radiation temperature sensor:


WFT-202(F1 quartz glass)400 ~ 1200℃


WFT-202(F2, K9 glass)700 ~ 2000℃


Output form


Two groups of relay contact output can be arbitrarily composed of the following modes:


1. Upper limit alarm


2. Lower limit alarm (two-position control)


3. Upper and lower limit alarm (three-position control)


4. Upper and upper limit alarm


5. Lower and lower limit alarm


The insensitive area of each pair of contacts is adjustable from 0 to 9999


The capacity of each pair of contacts is 3A, 220V AC, non-inductive load.


Power supply


Transformer power supply: 220V± 10% 50Hz to 60 Hz


Switching power supply: 86V ~ 264VAC 50Hz ~ 60Hz


Transmitter power supply: 24V, 30mA.DC